f4comex2.abm (F4-CP128-1)
10 REM ***
12 REM Example Communication Program for F4-CP128-1
14 REM
16 REM This is a generic example showing how to read data
18 REM from a serial device (scale, bar code, etc), parse numeric
20 REM data from the string and write the numeric data to the PLC
22 REM
24 REM This example assumes that the data is in the following format:
26 REM +########CRLF
100 REM ***
102 STRING 2551,254 : REM Allocate String Space 10*254 Strings
104 SETPORT 1,9600,N,8,1,N : REM Programming/Monitoring
106 SETPORT 2,9600,N,8,1,N : REM Scale
108 SETINPUT 1,1,10,0,1000,20 : REM Define how INPUT will work
110 REM —
112 PRINT1 “Waiting for Data”
130 REM —
132 INPUT2 ,$(0) : REM Input Data to String 0 ($(0))
134 IF INPLEN=0 THEN PRINT1 “Device Timed Out” : GOTO 130
136 X=VAL(MID$($(0),1,9)) : REM Parse Data from String
138 XHI=INT(X/10000) : XLO=X-(XHI*10000) : REM Seperate High/Low Word
140 S405_VB(2000)=XLO : REM Write Low Word
142 S405_VB(2001)=XHI : REM Write High Word
144 PRINT1 “Data= “,X
160 REM —
162 GOTO 130 : REM Loop